[. . . ] Installation 5. 1 Mechanical Connections 5. 2 Operating Diagram Page 44 45 46 47 47 48 49 50 50/51 52 53 54 55 56 57 57 58 58 59 6. Auxiliary Switches 6. @. 1 Mechanical Auxiliary Switches 6. @. 2 Inductive Auxiliary Switches 6. 2 Potentiometer 6. 3 Stroke Limiter 6. 4 Solenoid Pilot Valve Type PV 93 7. Introduction This instruction manual contains the description, technical data and instructions for installation, startup and maintenance of the pneumatic actuators PA @0 and PA 20 for ball valves type 220­227. Warnings: Any work done on the actuator may only be carried out by authorized and trained personnel. [. . . ] Installation of Supplementary Modular Components The pneumatic actuators PA @0 and PA 20 are equipped with fastening points for the installation of various supplementary modular components. A power plug is used for electrical connections for standard versions. The explosionproof version is equipped with a connecting cable 2 meters in length and 3 x 0. 75 mm 2 in cross-section. The modular components are prepared for installation; the electric wires are cut to length and ready to use. How to install and wire the components is illustrated on the following pages. 52 GEORGE FISCHER . . . 6. @ Auxiliary Switches The installation procedure is the same for all versions. q Unscrew the transparent cover and remove the fastening screws for the disk (postional indicator) q Install the switch in its position q Place the camshaft with switching cams on the disk and tighten the screws slightly q Adjust the camshaft using the eccentric bore so that the cams operate the switches properly even outside the end position q Tighten the camshaft screw firmly q Put the actuator in the «open» position and turn the lower switching cam counterclockwise to the switch lever q Put the actuator in the «closed» position and turn the upper cam clockwise to the switch lever q Install O-rings, housing and transparent cover q Use a 4-pole plug for the electrical connection 1 2 3 4 5 6 Camshaft Switching cams Limit switch «closed» Limit switch «open» Power plug Fastening position for additional auxiliary switches or potentiometer GEORGE FISCHER . . . 53 6. @. @ Mechanical Auxiliary Switches Description Kit with 2 additional auxiliary switches Kit with 2 additional auxiliary switches with gold contacts Kit with 2 additional auxiliary switches EExd II CT6 Technical Data 250 V, @0 A 4­30 V= @­@00 mA 250 V, 5 A Code 199 190 131 199 190 134 199 190 135 Wiring Diagram Close Open @99 @90 @31 @99 @90 @34 14 2 14 2 Close @99 @90 @35 Open black white black red white brown green 3 2 1 Both switches are pre-soldered for closing. Resoldering the connections from 4 to 2 results in an opening function. 54 GEORGE FISCHER . . . white brown green 6. @. 2 Inductive Auxiliary Switches The mechanical installation is the same as for those described in 6. @. The switches are activated via a metal trigger which changes the impedance of the circuit. Description Kit with 2 additional auxiliary switches Inductive with LED Kit with 2 additional auxiliary switches Inductive with LED Kit with 2 additional auxiliary switches Inductive Technical Data 9. 6­55 V= 0. 2 A 9. 6­55 V= 0. 2 A 5­24 V= @0 mA Code 199 190 136 199 190 137 199 190 133 NPN PNP Namur Wiring Diagram Close @99 @90 @36 @99 @90 @37 red white black green white black Open @99 @90 @33 Close Open 3 2 1 black white 2 1 black white 3 ­ + + NPN ­ PNP + ­ + ­ GEORGE FISCHER . . . 55 6. 2 Potentiometer Description Potentiometer kit Technical Data @000 /2 W Code @99 @90 @32 The potentiometer is used for continuous feedback on the ball valve position. Installation: q Unscrew the transparent cover and remove the fastening screws for the disk (positional indicator) q Install the potentiometer in its position q Place the shaft with the large gearwheel on the disk and screw on tightly q Put the actuator in the «closed» position q Turn the potentiometer with a screwdriver in the clockwise direction up to the stop so that there is 0- between the red and the white connecting wire q Install the O-rings, housing and transparent cover q Use a 4-pole plug for the electrical connection. CW CCW Wiring Diagram white @ Potentiometer 2 Shaft with gearwheel 3 2 1 56 GEORGE FISCHER . . . black red 6. 3 Stroke Limiter (available on request) Single acting Locknut Locknut Kontermutter Threaded stud Gewindestift Threaded stud 6. 4 Solenoid Pilot Valve Type PV 93 Description Technical Data Code Direct installation version (incl. 5 V, 50­60 Hz 24 V= 24 V, 50­60 Hz @99 @90 263 @99 @90 264 @99 @90 265 @99 @90 266 For installation on multiple manifold. 5 V, 50­60 Hz 24 V= 24 V, 50­60 Hz @99 @90 267 @99 @90 268 @99 @90 269 @99 @90 270 Multiple manifold 4 position 6 position 8 position Blank cover plate with @ O-ring and 2 screws @99 @90 271 @99 @90 272 @99 @90 273 @99 @90 274 Mode of operation: de-energized closed GEORGE FISCHER . . . 57 7. before connecting the actuator to the compressed air supply, the following points must be checked carefully: q Correct control pressure (max. 7 bar) q Correct connections q Correct sealing of control connections b) Adjustments: All valves assembled by George Fischer are fully adjusted and ready for operation. Standard versions of the PA @0 and PA 20 actuators have a mechanical rotation limited to 90°. In the case of assembly by the customer or after repairs, adjustments (e. g. of accessories) must be done and checked according to these instructions. Maintenance The PA @0/PA 20 pneumatic actuators have low maintenance. [. . . ] +46(0)8/727 47 00, Fax +46(0)8/749 23 70 e-mail: info@georgfischer. se, Internet: http://www. georgfischer. se George Fischer Pte. Ltd. , ¢5 Kaki Bukit Road 2, KB Warehouse Complex, 4¢7 845 Singapore/Singapore Tel. +65(0)7/47 06 ¢¢, Fax +65(0)7/47 05 77, e-mail: info@georgfischer. com. sg George Fischer Inc. , 2882 Dow Avenue, Tustin, CA 92780-7285 Tel. [. . . ]